CIRCUIT BREAKER
The main difference between a fuse and circuit breaker is
that under fault condition the fuse melts and it is to be replaced whereas the
circuit breaker can close or breaker the circuit without replacement.
Requirements of circuit breakers:-
The power association with the circuit breakers is large and
it forms the link between the consumers and supplies and suppliers. The
necessary requirements of circuit breakers are as follows
1.The normal working current and the short circuit
current must be safely interrupted by the circuit breaker
2.The faulty section of the system must be
isolated by circuit breaker as quickly as possible keeping minimum delay
3.It should not operate with flow of over current
during healthy conditions.
4. The faulty circuit only must be isolated without
affecting the healthy one.
BASIC ACTION OF A CIRCUIT BREAKER
As shown in fig the elementary diagram of a circuit breaker.
It consists of two contacts a fixed contact and a moving contact . A
handle is attached at the end of the
moving contacts. It can be operated manually or automatically. The automatic
operation needs a separate mechanism which consists of a tip coil. The trip
coil is energized by secondary of the current transformer. The terminals of
circuit breaker are brought to power supply.
Under normal condition working conditions the emf produced
in the secondary winding of the transformer is insufficient to energize the
trip coil completey for its operation. Thus the contacts remain in closed
position carrying the normal working current. The contacts can be opened
manually also by handle.
Under abnormal
or faulty conditions high current in the primary winding of the current
transformer induced sufficiently high emf in the secondary winding so the trip
coil is energized. This will start opening motion of the contacts. The contacts
are moved towards right away from fixed contacts.
As we have seen already the separation of contacts will not
lead to breaking or interruption of circuit as an arc is struck between the
contacts. The production of arc delays the current interruption and in addition
to this it becomes large amount of heat which may damage the system or the
breaker. Thus it becomes necessary to extinguish the arc as early as possible in
minimum time, so that heat produced will lie within the allowable limit. This will
also ensure that the mechanical stresses produced on the parts of circuit
breaker are less.
The time interval which is passed in between the
energization of the trip coil to the instant of contact separation is called
the opening time. It is dependent on fault current level.
The time interval from the contact separation to the
extinction of arc is called arcing time. It depends not only on fault current but
also on availability of voltage for maintenance of arc and mechanism used for
extinction of arc.